How much voltage do you lose in a 12 V cable?
A 12 V DC circuit with a 3 % limit: find the wire size that keeps the drop small over your cable length.
What you enter stays on your device while you use this tool. Opening a shared link sends the settings in its address to HowToolbox to prepare the page.
More options
Voltage drop
0.6897 V
10 A over 5 m of 2.5 mm² cable loses 0.6897 V, 5.75% of 12 V, leaving 11.31 V at the load: more than the 3% limit, so use a thicker wire.
- Drop as a share
- 5.75%
- Voltage at the load
- 11.31 V
- Heat lost in the cable
- 6.9 W
- Smallest size for 3%
- 4.79 mm² (AWG 10)
A 12 V DC circuit with a 3 % limit: find the wire size that keeps the drop small over your cable length.
How to use
- The circuit is set to 12 V DC, 10 A over 5 m of 2.5 mm². Enter your own current, length and wire size.
- Read the drop, and the smallest wire that keeps it within the limit.
Smallest copper wire for a 3 % drop on 12 V DC
Cross-section in mm² and the thinnest standard AWG gauge that is thick enough. Resistive estimate at 20 °C.
How it works
On a 12 V circuit a few tenths of a volt are a large share of the supply. The wire carries the current out and back, so the drop is 2 × I × R, with R = ρ × L ÷ A for one conductor (copper ρ = 1/58 Ω·mm²/m). The same drop in volts is a much larger share of 12 V than of 230 V.
The table below gives the smallest copper wire for a 3 per cent drop, which is 0.36 V on 12 V, by current and one-way length. The AWG gauge is the thinnest standard gauge that is thick enough. Doubling the length or the current doubles the wire you need.
This is a resistive estimate at 20 °C. Warm cables have more resistance, so real drops are a little higher. It does not size a cable for heating or protection: the current a cable may carry and the fuse come from your wiring regulations.
Worked example
How much voltage does 10 A lose over 5 m of 2.5 mm² copper on 12 V, and what wire would fix it?
- Drop: 2 × 10 A × 5 m ÷ 58 ÷ 2.5 mm² = 0.69 V, 5.7% of 12 V; 11.3 V is left at the load.
- To stay within 3%, the cross-section must be at least 4.8 mm², AWG 10.
0.69 V is lost; use at least 4.8 mm² (AWG 10).
Sources
- OpenStax University Physics, vol. 2, §9.3 Resistivity and ResistanceUsed for: formula
Frequently asked questions
Why does a 12 V circuit need such thick wire?
The same power takes ten times the current at 12 V compared with 120 V, and the volts lost in the wire grow with the current. Losing 0.36 V is already 3 % of 12 V, while on a 230 V circuit it would be a tiny fraction. For example, 10 A over 5 m of 2.5 mm² copper loses about 0.7 V, nearly 6 %.
Where does the 3 % limit come from?
Boat wiring guidance commonly allows 3 % for critical circuits such as navigation lights, electronics and pumps, and 10 % for less critical ones like cabin lighting. The calculator uses 3 %; open the extra options and set the largest drop to 10 to see the looser case.
Is the length one way or the round trip?
Enter the one-way length from the supply to the load. The calculator counts the current going out and coming back along two wires, so you do not double it yourself.
Does this also work for 24 V or 48 V?
Yes. Change the voltage and keep the supply on DC. For the same current the volts lost stay the same, but they are a smaller share of a higher voltage, so a 24 V circuit can use thinner wire for the same percentage.
Does a longer cable need a thicker wire?
Yes, in proportion: for the same drop, twice the length needs twice the cross-section. The table shows the sizes for 2, 5 and 10 m.
Next you might need
More in Electronics & cabling
- AC power calculator, private, runs on your device
- Battery life calculator, private, runs on your device
- E-series preferred values, private, runs on your device
- LED resistor calculator, private, runs on your device
- Logic gates, private, runs on your device
- RC circuit calculator, private, runs on your device