Skip to content

How much resistance does your wire have?

The resistance of a wire from its metal, length, thickness and temperature, compared across ten metals.

Size given as
mm²

Resistance

114.9 mΩ

Copper wire: 10 m of 1.5 mm² wire at 20 °C has a resistance of 114.9 mΩ.

Key values as a table
MetalResistance
Silver106 mΩ
Pure copper112 mΩ
Copper wire114.9 mΩ
Gold162.7 mΩ
Aluminium188 mΩ
Tungsten373.3 mΩ
Iron646.7 mΩ
Platinum706.7 mΩ
Constantan3.267 Ω
Nichrome7.333 Ω
Resistance per m
11.49 mΩ
Cross-section
1.5 mm² (about AWG 15)

The resistance of a wire from its metal, length, thickness and temperature, compared across ten metals.

How to use

  1. Choose the metal (copper wire is the usual one) and enter the length of the wire.
  2. Give the thickness as a cross-section in mm², as an AWG gauge or as a diameter.
  3. Under More options, set the wire's temperature. Drag the end of the highlighted bar to change the length and watch every metal follow.

Resistance of 10 m of copper wire at 20 °C

Cross-section (mm²)Resistance (Ω)
0.50.345
10.172
1.50.115
2.50.069
40.0431
60.0287
100.0172

How it works

A wire resists current because the moving electrons keep bumping into the metal's atoms. A longer wire means more bumps, so resistance grows in step with length; a thicker wire gives the current more room, so resistance falls as the cross-section grows. How easily a metal conducts is its resistivity.

The resistance is R = ρ × L ÷ A, where ρ (rho) is the resistivity, L the length and A the cross-section. Copper wire has ρ = 1/58 Ω·mm²/m, so 10 m of 1.5 mm² wire has R = 10 ÷ 58 ÷ 1.5 = 0.115 Ω. Metals resist more when warm: ρ grows by the factor 1 + α × (T − 20 °C), and for copper α ≈ 0.0039 per degree, so the same wire at 70 °C has about 20 % more resistance.

This is the resistance of a solid round conductor carrying direct current. Stranded wire is close to it; at high frequencies the current crowds to the surface and the resistance rises. Sources: OpenStax University Physics, volume 2, section 9.3, resistivities from Wikipedia's resistivity table and IEC 60028 for copper wire.

Frequently asked questions

Why do aluminium cables need to be thicker than copper?

Aluminium's resistivity is about 1.6 times copper's, so the same resistance needs about 1.6 times the cross-section. It is lighter and cheaper, which is why overhead lines use it.

What does AWG mean?

American Wire Gauge: a bigger number is a thinner wire, and every 3 gauges halve the cross-section. Sizes thicker than 0 are written 1/0 to 4/0; type them here as 0 to −3.

Does the result include plugs and connectors?

No. It covers the wire itself. Contact resistance at terminals, joints and connectors adds to the measured total.

How do I get the resistance of a cable with two wires?

Current goes out along one wire and back along the other, so double the length. For the voltage this costs, use the voltage drop calculator.

Should the diameter include the insulation?

No. Enter the metal conductor’s diameter only. Insulation does not carry current, and including it would make the calculated resistance too low.