How much voltage does your cable lose?
The voltage lost along a cable run, the voltage left at the load and the smallest wire within your limit.
What you enter stays on your device while you use this tool. Opening a shared link sends the settings in its address to HowToolbox to prepare the page.
More options
Voltage drop
6.621 V
16 A over 30 m of 2.5 mm² cable loses 6.621 V, 2.88% of 230 V, leaving 223.4 V at the load: within the 3% limit.
- Drop as a share
- 2.88%
- Voltage at the load
- 223.4 V
- Heat lost in the cable
- 106 W
- Smallest size for 3%
- 2.4 mm² (AWG 13)
The voltage lost along a cable run, the voltage left at the load and the smallest wire within your limit.
How to use
- Choose the supply (DC, single-phase or three-phase) and enter its voltage and the current the load draws.
- Enter the cable length one way, from the supply to the load, and the size of each conductor in mm² or AWG.
- Under More options, choose copper or aluminium and the drop you allow. Drag the load end in the drawing to see how far the cable can run.
Voltage drop at 16 A over 30 m and 230 V (copper, single-phase)
How it works
Every cable has a little resistance, and current through a resistance costs voltage. A long or thin cable, or a large current, leaves noticeably less voltage at the load than at the supply, and the lost part turns into heat in the cable. Motors then start harder, lamps dim and electronics may reset.
For DC and single-phase, the current goes out along one conductor and back along the other, so the drop is ΔV = 2 × I × R, where I is the current and R = ρ × L ÷ A the resistance of one conductor of length L and cross-section A (copper: ρ = 1/58 Ω·mm²/m). For a balanced three-phase load the drop between lines is ΔV = √3 × I × R. A 16 A load at the end of 30 m of 2.5 mm² copper loses 2 × 16 × 30 ÷ 58 ÷ 2.5 = 6.6 V, 2.9 % of 230 V.
This is a resistive estimate at 20 °C. Warm cables have a few per cent more resistance and large AC cables add reactance, so real drops are somewhat higher. It is not a cable sizing rule: the current a cable may carry, protection and the allowed drop come from your local wiring regulations. Sources: OpenStax University Physics, volume 2, section 9.3, and the conventions of IEC 60364-5-52.
Sources
- OpenStax University Physics, vol. 2, §9.3 Resistivity and ResistanceUsed for: formula
Frequently asked questions
Does a larger AWG number mean a thicker conductor?
No. A larger AWG number means a thinner conductor. Switch the size unit to AWG before entering the gauge.
Which voltage should I enter for a three-phase supply?
Enter the line-to-line voltage and the current in each line. The three-phase calculation assumes the load is balanced.
How do I reduce voltage drop?
Use a thicker cable, a shorter run or a higher supply voltage: the same power at a higher voltage needs less current. Doubling the cross-section halves the drop.
Why does a 12 V system need such thick cables?
The same power at 12 V takes about 19 times the current of 230 V, and a fixed number of volts lost is a far bigger share of 12 V. Short runs and thick cables keep the loss down.
Is the mm² input the cable diameter?
No. It is the cross-sectional area of one conductor, excluding insulation. A diameter in millimetres cannot be entered as though it were an area in square millimetres.
Next you might need
More in Electronics & cabling
- AC power calculator, private, runs on your device
- Battery life calculator, private, runs on your device
- E-series preferred values, private, runs on your device
- LED resistor calculator, private, runs on your device
- Logic gates, private, runs on your device
- RC circuit calculator, private, runs on your device